Multi-Channel Input
Single- and Dual-Alarm
Controllers
Installation and Operation Manual
Instruction 6709-9000
Revision 1 – October 25, 2012
Product Leadership Training Service Reliability
Vista de página 0
1 2 3 4 5 6 ... 31 32

Resumo do Conteúdo

Página 1

Multi-Channel Input Single- and Dual-Alarm Controllers Installation and Operation Manual Instruction 6709-9000 Revision 1 – October 25, 20

Página 2

MGS Series Controller Manual 10 6709-9000 Rev 1 NOTE: Figure 4 shows components associated with a dual-alarm configuration. For single-alarm co

Página 3

MGS Series Controller Manual 6709-9000 Rev 1 11 1.5. Specifications Specification 1-2 Channel 4-6 Channel Product Type 1-2 channel alarm contro

Página 4 - Table of Contents

MGS Series Controller Manual 12 6709-9000 Rev 1 Section 2. Mounting Instructions 2.1. Installation Warnings WARNING: Explosion hazard! Do not m

Página 5 - Section 1. Introduction

MGS Series Controller Manual 6709-9000 Rev 1 13 Sensors must be located within the appropriate wire lengths from the central control unit (if used)

Página 6

MGS Series Controller Manual 14 6709-9000 Rev 1 Figure 6. Mounting Dimensions (2-Channel Unit)

Página 7 - 6709-9000 Rev 1 7

MGS Series Controller Manual 6709-9000 Rev 1 15 Figure 7. Mounting Dimensions (6-Channel Unit)

Página 8 - 1.4. Components

MGS Series Controller Manual 16 6709-9000 Rev 1 Section 3. Wiring 3.1. 1- and 2-Channel Units (Single- and Dual-Alarm) Wiring to Sensors/Transmit

Página 9 - 6709-9000 Rev 1 9

MGS Series Controller Manual 6709-9000 Rev 1 17 NOTE: The potential from -Ve to +Ve is approximately 15 VDC. Figure 9. Wiring (2-Channel, Dual

Página 10 - 10 6709-9000 Rev 1

MGS Series Controller Manual 18 6709-9000 Rev 1 Figure 10. Wiring (6-Channel, Single-Alarm Unit Shown)

Página 11 - 1.5. Specifications

MGS Series Controller Manual 6709-9000 Rev 1 19 Figure 11. Wiring (6-Channel, Dual-Alarm Unit Shown) NOTE: An external horn is provided with 4

Página 12 - 12 6709-9000 Rev 1

MGS Series Controller Manual 2 6709-9000 Rev 1 WARRANTY POLICY BACHARACH, INC. WARRANTS THIS INSTRUMENT, EXCLUDING SENSORS, TO BE FREE FROM DEFECT

Página 13 - 2.3. Mounting Dimensions

MGS Series Controller Manual 20 6709-9000 Rev 1 3.3. External Horn (for Audible Alarms) Horn Specifications (Test Conditions at 25°C) Specificat

Página 14 - MGS Series Controller Manual

MGS Series Controller Manual 6709-9000 Rev 1 21 Section 4. Configuration and Operation 4.1. Overview The following topics are explained in this s

Página 15

MGS Series Controller Manual 22 6709-9000 Rev 1 POTs Used to Set Alarm Limits Max # Input Chans Number of Alarms Alarm Type P3 P7 P8 2 1 High

Página 16 - Section 3. Wiring

MGS Series Controller Manual 6709-9000 Rev 1 23 4.3. Changing Alarm Level for 2-Channel, 1-Alarm Units Step Instructions 1 Connect voltmeter lead

Página 17 - 6709-9000 Rev 1 17

MGS Series Controller Manual 24 6709-9000 Rev 1 4.4. Changing Alarm Level for 2-Channel, 2-Alarm Units Step Instructions 1 Connect voltmeter lead

Página 18

MGS Series Controller Manual 6709-9000 Rev 1 25 4.5. Changing Alarm Level for 6-Channel, 1-Alarm Units Step Instructions 1 Connect voltmeter lead

Página 19

MGS Series Controller Manual 26 6709-9000 Rev 1 4.6. Changing Alarm Level for 6-Channel, 2-Alarm Units Step Instructions 1 Connect voltmeter lead

Página 20 - 20 6709-9000 Rev 1

MGS Series Controller Manual 6709-9000 Rev 1 27 4.7. Output Delays Controllers with only single-level alarm capabilities use jumper JP1 to enab

Página 21 - 4.1. Overview

MGS Series Controller Manual 28 6709-9000 Rev 1 Figure 17. Alarm Response (Dual-Level Alarms) 4.8. Fail Safe Operation The JP1 jumper on the 6-

Página 22 - 22 6709-9000 Rev 1

MGS Series Controller Manual 6709-9000 Rev 1 29 4.9. Muting the Audible Alarm (Key Switch) If service is being carried out on the system or the u

Página 23 - 6709-9000 Rev 1 23

MGS Series Controller Manual 6709-9000 Rev 1 3 PRIOR TO SHIPPING EQUIPMENT TO BACHARACH, CONTACT OUR OFFICE FOR AN RMA # (RETURNED MERCHANDISE AUTH

Página 24 - 24 6709-9000 Rev 1

MGS Series Controller Manual 30 6709-9000 Rev 1 DECLARATION OF CONFORMITY The manufacturer of the products covered by this declaration: Bacharach

Página 25 - 6709-9000 Rev 1 25

MGS Series Controller Manual 6709-9000 Rev 1 31

Página 26 - 26 6709-9000 Rev 1

MGS Series Controller Manual 32 6709-9000 Rev 1 World Headquarters 621 Hunt Valley Circle, New Kensington, Pennsylv

Página 27 - 4.7. Output Delays

MGS Series Controller Manual 4 6709-9000 Rev 1 Table of Contents SECTION 1. INTRODUCTION ...

Página 28 - 4.8. Fail Safe Operation

MGS Series Controller Manual 6709-9000 Rev 1 5 Section 1. Introduction 1.1. Overview The MGS Series controllers provide local alarm status indica

Página 29 - ∇ ∇ ∇

MGS Series Controller Manual 6 6709-9000 Rev 1 Figure 1. Sample Configurations (1,2-Channel)

Página 30 - ONFORMITY

MGS Series Controller Manual 6709-9000 Rev 1 7 Figure 2. Sample Configurations (4,6-Channel) MGS Controllers have either one or two relay outputs

Página 31

MGS Series Controller Manual 8 6709-9000 Rev 1 Figure 3. Sample Front Panels Showing Status LEDs For dual-alarm configurations, the Alarm Low rel

Página 32 - World Headquarters

MGS Series Controller Manual 6709-9000 Rev 1 9 Components Descriptions Power input Provides power to the MGS Controller Power LED Power status i